Assignment title: Information
An 11 kV motor is fed by cables from a transformer via switchgear,
having a phase impedance of 0.3 + j0.3 ohm. The earth return path to
the transformer neutral has a resistance of 0.42 ohm. Determine a
suitable value of neutral resistance if the voltage rise at the motor in the
event of an earth fault at the motor is not to exceed 430 V. Neglect
transformer winding resistance.
3. Using TABLE 1, determine the resistance of a conductor and the volt
drop per ampere metre at 70°C for a 95 mm2 pvc/swa/pvc copper cable.
The temperature coefficient of resistance is 0.004 per °C.
Copper
Conductor
Size
6 mm2
10 mm2
16 mm2
25 mm2
35 mm2
50 mm2
70 mm2
95 mm2
120 mm2
150 mm2
185 mm2
240 mm2
300 mm2
Resistance/metre
of Conductor
(microhms per metre)
3080
1830
1150
727
524
387
268
193
153
124
99
75
60
Resistance/metre
of Steel Armour
(microhms per metre)
4600
3700
3200
2400
2100
1990
1400
1200
1100
740
680
600
540
TABLE 1 Resistances of Copper Conductor and Steel Wire Armour for
3-core copper PVC Insulated Cables at 20°C.
Teesside University Open Learning
(Engineering)
© Teesside University 2011
4
4. A load, 100 m from a 415 V Supply Authority point is connected by a
35 mm2 pvc/swa/pvc copper cable. The current rating is 119 A and the
volt drop per ampere metre is 1.1 mV. If the load current is 90 A,
determine whether the volt drop at the load is within the 17th Edition of
the IEE Wiring Regulations 5% limit. Using TABLE 1, calculate the
earth loop impedance, minimum fault current (neglect the supply/earth
impedance) and select an appropriate fuse for the circuit with reference to
B.S. 88 part 2 (see FIGURE 3, Lesson 4 - 4).